Diagnosis

Diagnosis of Power Plants Facilities & Extra Hig Voltage Power Utility

Introduction :

  • Diagnosis to improve reliability through testing protection system including protective relay during the installment, repair of power plants facilities

Diagnosis object :

  • Thermal Power, Hydro Power, etc
  • A cogeneration plant for local district heating
  • General generation facility of indust rial utillity
  • 345KV high Voltage transmission, Substation and Incoming transformer facility

Contents :

  • Protective relay test (Pick up, Characteristic test etc)
  • AC & DC Sequence test
  • Interlock and Active loads phase test
  • Current, voltage transformer test
  • Transducer characteristic test
  • Alarm receiving equipment and Data Logger test
  • Event & Fault Recorder test
  • Interlock test on Detection & Control facility

Expected Effect :

  • Consulting about the optimized protect ion power facility
  • Improving stability of power supply and credibility of protective equipment

Diagnosis Photo :

Diagnosis Photo - Rrotection Relay Tester, CT Tester

Diagnosis of Renewable Energy Electrical Facilities

Introduction :

  • Testing of electrica I installation of re newable energy that is rapidly in creasing in accordance with the recent instability of oil prices and countermeasure for the Climate Change Convention

Diagnosis object :

  • Generation facility using solar, wind, water, LFG, bio gas and fuel cell etc

Contents :

 
ObjectContent
Relay
  • Unit Protection Feeder Relay
    - Pick up test, performance characteristic test
  • AC & DC Sequence test
CT

Primary Injection Test and Saturating Test
- Metering test       - Bus diff. Test      - Ratio Test      - Polarity Test      - Secondary circuit check

VT

Characteristic test
- Ratio Test      - Secondary circuit check

Cable
  • AC Insulation Diagnosis
  • DC Insulation Diagnosis
Tr

AC Insulation Diagnosis
- measuring power loss of insulation object (Managing trend through a regular diagnosis)

Expected Effect :

  • Confirming proper construction of incoming substation facilities
  • Consultiong about maintenance of electrical facilities
  • A quick problem - solving in case of accident

Diagnosis Photo :

Diagnosis Photo

Diagnosis of Marine Electrical Facilities

Introduction :

  • Testing of marine electrical fac ilit ies owned by renowned overseas oil developers whose contracts are won by Korean shipbuilders

Diagnosis object :

  • Marine electrical facilities equipped with bulk electrical facilities that is not subject to the Ships Act in Korea
  • A stationary platform of exploiting natural gas and crude oil, RIG, FPSO etc

Contents :

 
ObjectContent
Relay

Secondary injection Test and Setting Value Programming
- Generator, Feeder, Tr, Protective Relay etc

CT

Primary Injection Test and Saturating Test
- Metering test      - Bus diff. Test      - Ratio Test      - Polarity Test      - Secondary circuit check

VT

Characteristic test
- Ratio Tes      - Secondary circuit check

 

Bus Bar

Microhm Test

Generator

Measuring a change of voltage and frequency when generator load test

ACB

Protector trip test, Relay setting

Cable
  • AC Insulation Diagnosis
  • DC Insulation Diagnosis
Switch Gear

Wiring check, Inter-locking Check, Bus-bar Low Resistance Measurements

Cable

Partial Discharge Test, DC/AC Insulation Test etc

Achievements :

 
Ship OwnerProjectOverviewClient
Odebridge (Brazil) 2010 - 2011 OOG Drill Ship #1, 2, 3, 4 Commissioning DSME
TOTAL (France) 2009 - 2010 Pazflor FPSO Commissioning DSME
Odfjell (Netherlands) 2009 Lig Ship Commissioning DSME
Transocean (USA) 2009 Drill Ship #1, 2, 3, 4, 5 Commissioning DSME
Chevron (USA) 2008 Tombua Landana Commissioning DSME
Chevron (USA) 2006 2007 Agbami FPSO Commissioning DSME
TOTAL (France) 2006 Dalia Commissioning DSME
Exxon-Mobile (USA) 2005 East Area Commissioning DSME
BP (USA) 2004 Atlantis Commissioning DSME
Exxon-Mobile (USA) 2004 KIJOMBA - B Commissioning DSME

Measurement of Mesh Grounding Resistance

Introduction :

Measuring mesh grounding resistance can get a correct value only by test current supply method voltage drop, and the value should be maintained below standard by measuring regularly while not only completing but also utilizing eletrical facilities

Diagnosis method :

Selecting the place of valtage, current assistant pole → Arranging the minimum test current value → Arranging the capacity of the test current source → Selecting a node to measure voltage and inflow of current → alculating grounding resistance

Diagnosis object :

  • Large - scale earthing structure
  • Mesh grounding at an electric power substation
  • A grounding pole used as construction structure

Expected effect :

Reducing errors of measuring value due to inductive disturbance from the outside

Diagnosis method wiring map :

Mesh grounding     C:Current assistant pole      P:Voltage assistant pole

Diagnosis method wiring map